VFD Cable with EMC Screening

Application

EMC VFD cable has been specially designed for Variable Frequency Drive Motors and installations where it is necessary to limit the effects of electromagnetic interference (EMI).

Construction

Conductor Electrolytic copper,class 5 (flexible),based on EN/IEC 60228
Grouding Conductor The grounding conductor is divided into three conductors; the equivalent cross section is approximately 50% of the section of the phase conductor.
Insulation Cross-linked polyethylene (XLPE) 4G grey + brown + black + Green/yellow (up to 4 mm2) 3x + 3G grey + brown + black + Green/yellow (3 x) (from 6 mm2 onwards)
Screen Aluminium-polyester tape screen, helically placed over the insulated conductors. Over the tape there is a tinned copper braid screen. The tape and the braid act as a double screen to cut out all of the the electromagnetic interference. The screen has a cover of 100% and its total section is approximately 10% of one of the conductors.
Outer Jacket Polyolefin LSZH outer sheath with ripcord to allows for ease of stripping of the outer jacket.

Technical Information

Electrical performance LOW VOLTAGE 0.6/1 KV
Standrd IEC 60502-1 / IEC 60092-353
Thermal performance Maximum service temperature: 90ºC.
Maximum short-circuit temperature: 250ºC (max. 5 s).
Minimum service temperature: -40ºC (fixed and protected installations).
Fire performance  
Flame non-propagation based on UNE-EN 60332-1 and IEC 60332-1.
Fire non-propagation based on UNE-EN 60332-3 and IEC 60332-3.
LSZH(Low Smoke Zero Halogen) based on UNE-EN 60754-1 and IEC 60754-1.
Low smoke emission based in UNE-EN 61034 and IEC 61034:Light transmittance>60%
Low corrosive gases emission based on UNE-EN 60754-2 and IEC 60754-2.
Mechanical performance  
Minimum bending radius: x10 cable diameter.
Impact resistance: AG2 Medium severity.
Chemical performance Chemical & Oil resistance: Good.
Water performance Water resistance: AD5 Jets.
Installation conditions Open Air. Buried. In conduit.
Applications Industrial use. Variable Frequency Drive (VFD)

Cable Parameter

No.of cores x cross section Outer-Ø ca.mm Copper weight Cable weight approx. AWG
n x mm2 ± 10% kg/km kg/km  
4G1.5 10.6 95 230 16
7G1.5 12.9 151 362 16
4G2.5 12.3 150 300 14
7G2.5 14 265 450 14
4G4 14.5 235 485 12
4G6 16.2 320 633 10
4G10 19.2 533 863 8
4G16 22 789 1291 6
4G25 27 1236 1862 4
4G35 30 1662 2611 2
4G50 35 2345 2955 1
4G70 40.8 3196 3953 2/0
4G95 45.8 4316 5304 3/0
4G120 49.7 5435 6604 4/0
4G150 57 6394 7043 250 MCM
4G185 61.1 7639 8384 350 MCM
4G240 67 10013 11010 450 MCM
4G300 71.5 12570 13800 550 MCM
3x1.5+3G0.25 10.2 86 140 16/24
3x2.5+3G0.5 11.4 144 220 14/20
3x4+3G0.75 13 224 323 12/19
3x6+3G1 15 298 420 10/18
3x10+3G1.5 18.4 491 615 8/16
3x16+3G2.5 21.6 723 819 6/14
3x25+3G4 25.3 1000 1200 4/12
3x35+3G6 27.8 1350 1600 2/10
3x50+3G10 32.6 2208 2399 1/8
3x70+3G10 39 2871 3080 2/0/8
3x95+3G16 44.3 3953 4180 3/0/6
3x120+3G16 46.3 4300 4700 4/0/6
3x150+3G25 53.5 5450 5900 250 MCM/4
3x185+3G35 59.5 6969 7189 350 MCM/2
3x240+3G42.5 65.2 8850 9540 450 MCM/1
3x300+3G50 69.5 10700 11560 550 MCM/1