HomeProuductsTelecommunication cables

Auxiliary Multipair Cables - ARMOUR SCREEN PVC

DESCRIPTION

Copper, Multi Pair, PVC-Insulation, Collective, Armour, PVC Sheath

APPLICATION

These light current control cables are intended primarily for use with control, indication and alarm equipment for switchgear and similar power apparatus in power stations and substations. Suitable for use on circuits where the nominal voltage does not exceed 150V d.c. or 110V a.c. Suitable for direct buried applications.

STANDARD

ENATS 09-6 ISSUE 9

CABLE CONSTRUCTION

Conductors : Solid (Class 1) tinned copper conductors to BS EN 60228.

Insulation : PVC insulation to BS7655.

Pair Identification : See colour code.

Binder Tape : p.e.t.p. tape of suitable overlap.

Collective Screen : tinned copper drain wire under and in contact with aluminium/p.e.t.p. laminated tape applied metallic side down.

Inner Sheath : PVC inner sheath to BS7655.

Armouring : Mild galvanised steel wires to BS EN10257-1.

Outer Sheath : Black PVC outer sheath Type to BS7655 .

Voltage Rating : 150V d.c./110V a.c.

Temperature Rating : 70°C maximum conductor operating temperature.

ELECTRICAL DATA @ 20ºC

Conductor size Nom mm² 0,5
Conductor resistance (Solid / Class 1) Max Ω/km 36
Insulation resistance Individual conductor Min. MΩxkm 80
Screen and armour Min. MΩxkm 1
Mutual capacitance 1kHz (core to core) Max. nF/km 150
Mutual inductance Max. µH/Ω 50
Test voltage Ums core: core V 2000
  Ums core: armour V 2000

PROPERTIES FOR CABLE

Code Colour ENATS 09-6 Issue 9 * Table 1
Fire Resistant N.A.
Flame Retardant IEC 60332-3-24
Low Smoke Emision N.A.
Other Properties  
Minimum Bending Radius 10 X O.D.

PROPERTIES FOR OUTER SHEATH

Limiting Oxygen Index N.A.
Amount of halogen acid gas HCl<15%
Oil Resistance N.A.
Sunlight Resistance UL 1581 Section 1200
Temperature Installation -5ºC/50ºC
Temperature Operating -30ºC/50ºC

CONSTRUCTION PARAMETERS

No. Pairs Cores RT Insulation Nominal RT Inner sheath Ø over inner sheath Ø of armour wire nom. RT of outer sheath nom. Overall diameter Weight approx.
  mm² mm mm mm mm mm mm kg/km
2 0.5mm² 0,3 0,8 5,37 0,9 1,3 9,77 207
5 0.5mm² 0,3 1,0 8,84 0,9 1,4 13,44 364
10 0.5mm² 0,3 1,1 11,56 1,25 1,5 17,06 616
20 0.5mm² 0,3 1,2 15,01 1,25 1,6 20,71 887
40 0.5mm² 0,3 1,4 23,96 1,6 1,8 30,76 1731
60 0.5mm² 0,3 1,6 25,94 1,6 2,0 33,14 2134
100 0.5mm² 0,3 1,9 32,28 2 2,2 40,68 3314

CODE COLOUR ENATS 09-6 ISSUE 9 TABLE 1

2 Pair Cable (quad)

1 White Red Blue Orange

5 Pair Cables to 20 Pair Cables

1 White Blue 11 Black Blue
2 White Orange 12 Black Orange
3 White Green 13 Black Green
4 White Brown 14 Black Brown
5 White Grey 15 Black Grey
6 Red Blue 16 Yellow Blue
7 Red Orange 17 Yellow Orange
8 Red Green 18 Yellow Green
9 Red Brown 19 Yellow Brown
10 Red Grey 20 Yellow Grey

For 40 pairs cables – Pairs 1 to 20, two times

For 60 pairs cables – Pairs 1 to 20, three times

For 100 pairs cables – Pairs 1 to 20, five times