Home ProuductsIndustrial Cables

American Standard UL Industrial Cables
TW

Application and Description

The TW conductor is suitable for most current wiring solutions for residential, commercial and industrial environments. It is used in branch circuits for permanent installations. TW conductors in sizes 14 AWG to 8 AWG can be installed in conduits and other raceways. The temperature of installation shall not exceed 60ºC.

Cable Construction

Conductor:
Bare annealed copper conductor, solid or stranded
Insulation:
PVC 60°C insulation
Color:
upon request, black is preferable

Industrial Cables TW

Technical Compliances

- ASTM B3, B8
- UL 83 - Thermoplastic-Insulated Wires and Cables
- UL 1581 - Electrical Wires, Cables and Flexible Cords

Cable Parameter

AWG or kcmil Strand Nominal Insulation Thickness Inch/mm Nominl Overall Diameter Inch/mm Cable Weight Lbs/kft  kg/km
14 1 0.030 0.76 0.138 3.5 19 28
12 1 0.030 0.76 0.154 3.9 27 40
10 1 0.030 0.76 0.177 4.5 40 60
8 1 0.045 1.14 0.240 6.1 67 100
14 7 0.030 0.76 0.146 3.7 19 29
12 7 0.030 0.76 0.165 4.2 29 43
10 7 0.030 0.76 0.193 4.9 44 65
8 7 0.045 1.14 0.260 6.6 72 107