PRODUCTS
- Aerial Bundled Cables
- Airport Cables
- Automotive Cables
- Alarm & Audio & Electronic Cables
- Belden Equivalent Cables
- Bus Cables
- Cable Glands
- Cables for Oil Industry
- Coaxial Cables
- Composite Cables
- Control Cables
- Data Cables
- Elevator Cables
- Fiber Optic Cables
- Fire Resisting Cable(Fireflix)
- Fire Retardant Cable(FIRETOX)
- Flame Retardant Cable (FIREGUARD)
- Flexible Cables
- Heat Detection Cables
- High Temperature Cables
- Highway Cables
- Industrial Cables
- Instrumentation Cables
- Marine Cable
- NEK606 Water Blocked Offshore & Marine Cables
- IEC60092 STANDARD Offshore & Marine Cables
- BS 6883&BS7917 STANDARD Offshore & Marine Cables
- UKOOA Offshore & Marine cables
- VG 95218 Navy Cables
- Mining Cables
- Airframe Wire
- Marine, OIL,GAS & Petrochemical Cables
- Power Cables
- Railway Cables
- Robotics
- Rolling Stock Cables
- Rubber & Crane Cables
- Security Cables
- Special Cables
- Spiral Cables
- Telephone Cables
- Thermocouple Cables
- BS 5308 Cable
- PAS 5308 Cable
- BS 5467 Cable
- BS 6724 Cable
- BS 6346 Cable
- BS 7211 Cable
- IEC 60502-1 Cable
HOT PRODUCTS
APPLICATIONS
|
EPR/HYP, Low-Voltage Power, Unshielded 600V, UL Type
RHH/RHW-2/USE-2 LS
Application
These cables are suited for use in a broad range of commercial, industrial and utility applications where reliability is a major concern and where maximum performance will be demanded, in free air, raceways or direct burial and in aerial, conduit, open tray and underground duct.
Standard:
Industry Standard:
National Electric Code (NEC)
ICEA S-95-658 / NEMA WC70
FOR CT USE on 1/0 AWG and larger in accordance with the NEC
UL 44 Type RHH/RHW-2
UL 854 Type USE-2
Low-smoke rating per UL
Flame Tests Standard:
UL 1581 VW-1
For 1/0 AWG and larger: IEEE 383, IEEE 1202/CSA FT-4
Other Standard:
EPA 40 CFR, Part 261 for leachable lead content per TCLP
Cable Construction
Conductor: Tin-coated copper compressed Class B stranding per ASTM B33.
Insulation: Flame-retardant Ethylene Propylene Rubber (EPR) colored for contrast with
black low-lead Chlorosulfonated Polyethylene (CSPE)/Elastomer blend.
Cable Parameter
CON. Size (AWG/ kcmil) |
CON. Strand |
Nominal CON. Diameter |
MIN. AVG. Insulation |
MIN. AVG. Jacket |
Appr. Cable Weight | ||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Thickness | Diameter | Thickness | Diameter | ||||||||||
Inches | mm | Inches | mm | Inches | mm | Inches | mm | Inches | mm | LBS/ 1000 FT |
kg/km | ||
14 | 7/0.0242 | 0.07 | 1.78 | 0.030 | 0.76 | 0.14 | 3.56 | 0.015 | 0.38 | 0.17 | 4.32 | 24 | 36 |
12 | 7/0.0305 | 0.09 | 2.29 | 0.030 | 0.76 | 0.16 | 4.06 | 0.015 | 0.38 | 0.19 | 4.83 | 33 | 49 |
10 | 7/0.0385 | 0.12 | 3.05 | 0.030 | 0.76 | 0.18 | 4.57 | 0.015 | 0.38 | 0.21 | 5.33 | 48 | 71 |
8 | 7/0.0486 | 0.15 | 3.81 | 0.045 | 1.14 | 0.24 | 6.10 | 0.015 | 0.38 | 0.28 | 7.11 | 77 | 115 |
6 | 7/0.0612 | 0.18 | 4.57 | 0.045 | 1.14 | 0.28 | 7.11 | 0.030 | 0.76 | 0.35 | 8.89 | 122 | 182 |
4 | 7/0.0772 | 0.23 | 5.84 | 0.045 | 1.14 | 0.33 | 8.38 | 0.030 | 0.76 | 0.39 | 9.91 | 178 | 265 |
2 | 7/0.0974 | 0.29 | 7.37 | 0.045 | 1.14 | 0.39 | 9.91 | 0.030 | 0.76 | 0.46 | 11.68 | 265 | 394 |
1/0 | 19/0.0740 | 0.37 | 9.40 | 0.055 | 1.40 | 0.48 | 12.19 | 0.045 | 1.14 | 0.58 | 14.73 | 422 | 628 |
2/0 | 19/0.0837 | 0.41 | 10.41 | 0.055 | 1.40 | 0.53 | 13.46 | 0.045 | 1.14 | 0.63 | 16.00 | 518 | 771 |
4/0 | 19/0.1055 | 0.52 | 13.21 | 0.055 | 1.40 | 0.64 | 16.26 | 0.045 | 1.14 | 0.74 | 18.80 | 785 | 1168 |
250 | 37/0.0822 | 0.56 | 14.22 | 0.065 | 1.65 | 0.70 | 17.78 | 0.065 | 1.65 | 0.85 | 21.59 | 960 | 1429 |
350 | 37/0.0973 | 0.67 | 17.02 | 0.065 | 1.65 | 0.81 | 20.57 | 0.065 | 1.65 | 0.96 | 24.38 | 1299 | 1933 |
500 | 37/0.1162 | 0.80 | 20.32 | 0.065 | 1.65 | 0.94 | 23.88 | 0.065 | 1.65 | 1.09 | 27.69 | 1803 | 2683 |
750 | 61/0.1109 | 0.98 | 24.89 | 0.080 | 2.03 | 1.15 | 29.21 | 0.065 | 1.65 | 1.31 | 33.27 | 2664 | 3965 |
1000 | 61/0.1280 | 1.13 | 28.70 | 0.080 | 2.03 | 1.31 | 33.27 | 0.065 | 1.65 | 1.46 | 37.08 | 3989 | 5936 |