Home ProuductsIndustrial Cables

American Standard UL Industrial Cables
RHH/RHW, copper, 2000V

Industrial Cables RHH/RHW, copper, 2000V

Application and Description

Type RHH, RHW-2 copper wire is suitable for wiring in raceways, conduit, etc. Applications include general purpose wiring for power distribution, services, feeders, and branch circuit wiring in residential, industrial, and commercial buildings.

Cable Construction

Conductor:
Stranded bare annealed soft copper
Insulation:
Flame-retardant, abrasion, moisture and heat resistant Cross-Linked Polyethylene (FRXLPE)
Color:
upon request, black is preferable

Technical Compliances

- UL 44 - Thermoset-Insulated Wires and Cables
- UL 854 - Service Entrance Cables.
- UL 1685 - UL Flame Exposure Test
- ICEA S-95-658 (NEMA WC70)

Cable Parameter

AWG or kcmil Strand Nominal insulation Thickness Inch/mm Nominal Overall Diameter Inch/mm Cable
Weight
Lbs/kft kg/km
14 7 0.060 1.52 0.193 4.90 25 37
12 7 0.060 1.52 0.212 5.38 34 51
10 7 0.060 1.52 0.236 5.99 48 71
8 7 0.070 1.78 0.286 7.26 73 109
6 7 0.070 1.78 0.324 8.23 106 158
4 7 0.070 1.78 0.372 9.45 158 235
3 7 0.070 1.78 0.4 10.16 195 290
2 7 0.070 1.78 0.432 10.97 240 357
1 19 0.090 2.29 0.501 12.73 310 461
1/0 19 0.090 2.29 0.54 13.72 382 568
2/0 19 0.090 2.29 0.584 14.83 472 702
3/0 19 0.090 2.29 0.634 16.10 586 872
4/0 19 0.090 2.29 0.69 17.53 728 1083
250 37 0.105 2.67 0.785 19.94 871 1296
300 37 0.105 2.67 0.839 21.31 1,033 1537
350 37 0.105 2.67 0.891 22.63 1,195 1778
400 37 0.105 2.67 0.938 23.83 1,357 2019
500 37 0.105 2.67 1.023 25.98 1,677 2495
600 61 0.120 3.05 1.131 28.73 2,021 3007
750 61 0.120 3.05 1.238 31.45 2,501 3721