PRODUCTS
- Aerial Bundled Cables
- Airport Cables
- Automotive Cables
- Alarm & Audio & Electronic Cables
- Belden Equivalent Cables
- Bus Cables
- Cable Glands
- Cables for Oil Industry
- Coaxial Cables
- Composite Cables
- Control Cables
- Data Cables
- Elevator Cables
- Fiber Optic Cables
- Fire Resisting Cable(Fireflix)
- Fire Retardant Cable(FIRETOX)
- Flame Retardant Cable (FIREGUARD)
- Flexible Cables
- Heat Detection Cables
- High Temperature Cables
- Highway Cables
- Industrial Cables
- Instrumentation Cables
- Marine Cable
- NEK606 Water Blocked Offshore & Marine Cables
- IEC60092 STANDARD Offshore & Marine Cables
- BS 6883&BS7917 STANDARD Offshore & Marine Cables
- UKOOA Offshore & Marine cables
- VG 95218 Navy Cables
- Mining Cables
- Airframe Wire
- Marine, OIL,GAS & Petrochemical Cables
- Power Cables
- Railway Cables
- Robotics
- Rolling Stock Cables
- Rubber & Crane Cables
- Security Cables
- Special Cables
- Spiral Cables
- Telephone Cables
- Thermocouple Cables
- BS 5308 Cable
- PAS 5308 Cable
- BS 5467 Cable
- BS 6724 Cable
- BS 6346 Cable
- BS 7211 Cable
- IEC 60502-1 Cable
HOT PRODUCTS
APPLICATIONS
|
EPR/AIA/PVC, Power, Non-Shielded, Armored 2400V, UL
Type MV-90 or MC, Three Conductor
Application
These cables are suited for use in a broad range of commercial, industrial and utility applications, where maximum performance is demanded, ease of installation desired and fire resistance is critical. Also they are permitted for use in Class I, Class II, Division 2, Class III Division 1 and 2 hazardous locations per the NEC, which are installed in both exposed or concealed work, wet or dry locations, indoors or outdoors and cable trays.
Standard:
National Electric Code (NEC)
ICEA S-96-659/NEMA WC-71
UL Listed as Type MV or Type MC
UL 1072
UL 1569
IEEE 1202 (70,000 BTU/hr)
IEEE 383 (70,000 BTU/hr)
UL 1581 (70,000 BTU/hr)
ICEA T-29-520 (210,000 BTU/hr)
ICEA T-30-520 (70,000 BTU/hr)
Meets EPA 40 CFR part 261 for leachable lead content per TCLP method
Cable Construction
Conductors: Bare copper, Class B strand.
Extruded Strand Shield (ESS): Extruded thermoset semi-conducting stress control layer
over conductor.
Insulation: Ethylene Propylene Rubber (EPR) colored to contrast with black conducting
shield layer.
Ground: Annealed bare copper Class B stranding per ASTM B8.
Armor: Aluminum Interlocked Armor (AIA).
Jacket: Flame-retardant Polyvinyl Chloride (PVC), UV resistance, hydrocarbon resistance,
oil resistance, anti rodent and anti termite properties can be offered as option—Yellow.
Cable Parameter
NO. of CON. |
CON. Size (AWG) |
CON. Diameter Inches |
GRND. Wire Size (AWG) |
Min. Insulation Thickness |
Appr.Armor O.D. | Nominal Jacket Thickness |
Appr. Cable O.D. |
Appr. Cable Weight | |||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Inches | mm | Inches | mm | Inches | mm | Inches | mm | LBS/ 1000 FT |
kg/km | ||||
3 | 6 | 0.17 | 6 | 0.115 | 2.92 | 1.16 | 29.4 | 0.050 | 1.27 | 1.27 | 32.2 | 854 | 1272 |
3 | 4 | 0.21 | 6 | 0.115 | 2.92 | 1.26 | 31.9 | 0.050 | 1.27 | 1.37 | 34.7 | 1056 | 1572 |
3 | 2 | 0.27 | 6 | 0.115 | 2.92 | 1.37 | 34.8 | 0.050 | 1.27 | 1.48 | 37.6 | 1363 | 2030 |
3 | 1/0 | 0.34 | 4 | 0.115 | 2.92 | 1.61 | 41.0 | 0.060 | 1.52 | 1.74 | 44.3 | 2003 | 2982 |
3 | 2/0 | 0.38 | 4 | 0.115 | 2.92 | 1.71 | 43.3 | 0.060 | 1.52 | 1.84 | 46.6 | 2326 | 3463 |
3 | 4/0 | 0.48 | 3 | 0.115 | 2.92 | 1.92 | 48.7 | 0.060 | 1.52 | 2.05 | 52.0 | 3256 | 4848 |
3 | 250 | 0.52 | 3 | 0.115 | 2.92 | 2.00 | 50.7 | 0.060 | 1.52 | 2.13 | 54.1 | 3689 | 5493 |
3 | 350 | 0.62 | 2 | 0.115 | 2.92 | 2.21 | 56.0 | 0.060 | 1.52 | 2.34 | 59.3 | 4825 | 7184 |
3 | 500 | 0.74 | 1 | 0.115 | 2.92 | 2.46 | 62.6 | 0.075 | 1.91 | 2.63 | 66.7 | 6567 | 9778 |
3 | 750 | 0.91 | 1/0 | 0.115 | 2.92 | 2.83 | 72.0 | 0.075 | 1.91 | 3.00 | 76.1 | 9320 | 13877 |
3 | 1000 | 1.07 | 1/0 | 0.115 | 2.92 | 3.16 | 80.3 | 0.085 | 2.16 | 3.35 | 85.0 | 12023 | 17902 |