Home ProuductsIndustrial Cables

TRXLPE/Tape Shield/PVC/AIA/PVC, Power, Shielded,
Armored 15KV, CSA HVTECK, 100% Ins. Level, 175 Mils,
Three Conductor

Application

These cables are used in ventilated, non-ventilated and ladder type cable trays in dry, damp or wet locations, direct earth burial (with protection as required by inspection authority). They are exposed and concealed wiring in dry, damp or wet locations. Besides,the wires are in all hazardous locations when used with certified HL cable glands.

Standard:

CSA FT1 and FT4
IEEE 383 (70,000 BTU/hr)
UL 1581(70,000 BTU/hr)
IEEE 1202 (70,000 BTU/hr) CSA FT4
ICEA T-30-520 (70,000 BTU/hr)
ICEA T-29-520 (210,000 BTU/hr)
Hazardous location rating: HL
CSA Standard C68.3
CSA Standard C22.2 No. 174
CSA Approval (file) numbers: LR27161
Meets EPA 40 CFR, part 261 for leachable lead content per TCLP method

Cable Construction

Conductor: Bare copper Class B strand.
Strand Shield: A thermoset semi-conducting strand shield is extruded over the conductor.
Insulation: Tree-Retardant Cross-Linked Polyethylene (TR-XLPE).
Insulation Shield: This consists of a semi-conducting thermosetting layer, applied in a triple extrusion process, plus a helically applied gapped copper tape.
Color-Coded: Black, Red or Blue colored tape placed longitudinally under the copper tape shield.
Ground (Bonding) Conductor: The conductor consists of one uninsulated stranded bare copper conductor.
Inner Jacket: Flame-retardant Polyvinyl Chloride (PVC), UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option— Black.
Armor: Aluminum Interlocked Armor (AIA).
Overall Jacket: Flame-retardant Polyvinyl Chloride (PVC), UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option—Red.

5kv CSA HVTECK

Cable Parameter

CON.
Size
(AWG)
Ground
Wire Size
AWG
Nominal Diameter (over) Appr. Cable Weight
W/AL Armor
Ampacity
(40°C
Ambient)
Insulation Insulation
Shield
Inner
Jacket
Armor CABLE LBS/
1000
FT
kg/km
Inches mm Inches mm Inches mm Inches mm Inches mm AL Steel AL Steel
2 6 0.66 16.76 0.73 18.54 1.82 46.3 2.11 53.6 2.21 56.2 2370 3220 3530 4790 164
1 6 0.69 17.53 0.76 19.30 1.89 48.0 2.18 55.4 2.27 57.7 2620 3490 3890 5190 187
1/0 6 0.73 18.54 0.79 20.07 1.97 50.0 2.26 57.4 2.35 59.7 2900 3810 4320 5670 215
2/0 6 0.77 19.56 0.84 21.33 2.06 52.3 2.34 59.5 2.46 62.5 3330 4280 4960 6370 246
3/0 4 0.82 20.83 0.88 22.35 2.16 54.9 2.44 62.0 2.57 65.3 3840 4840 5720 7200 283
4/0 4 0.87 22.10 0.93 23.62 2.27 57.7 2.56 65.1 2.68 68.1 4360 5410 6490 8050 325
250 4 0.93 23.62 0.99 25.15 2.38 60.5 2.68 68.1 2.79 70.9 4880 5990 7260 8910 359
350 3 1.06 26.92 1.15 29.21 2.73 69.4 3.02 76.7 3.14 79.8 6210 7430 9240 11060 438
500 3 1.14 28.96 1.23 31.24 2.97 75.5 3.26 82.8 3.40 86.4 8549 9550 12721 14200 536
750 2 1.32 33.53 1.41 35.81 3.35 85.1 3.64 92.5 3.77 95.8 11100 12640 16520 18810 669
1000 1 1.47 37.34 1.56 39.62 3.72 94.5 3.97 100.8 4.17 105.9 13890 15580 20670 23180 770