Home ProuductsIndustrial Cables

TRXLPE/Tape Shield/PVC/AIA/PVC, Power, Shielded,
Armored 5KV, CSA HVTECK, 133% Ins. Level, 115 Mils,
Three Conductor

Application

These cables are used in ventilated, non-ventilated and ladder type cable trays in dry, damp or wet locations, direct earth burial (with protection as required by inspection authority). They are exposed and concealed wiring in dry, damp or wet locations. Besides,the wires are in all hazardous locations when used with certified HL cable glands.

Standard:

CSA FT1 and FT4
IEEE 383 (70,000 BTU/hr)
UL 1581(70,000 BTU/hr)
IEEE 1202 (70,000 BTU/hr) CSA FT4
ICEA T-30-520 (70,000 BTU/hr)
ICEA T-29-520 (210,000 BTU/hr)
Hazardous location rating: HL
CSA Standard C68.3
CSA Standard C22.2 No. 174
CSA Approval (file) numbers: LR27161
Meets EPA 40 CFR, part 261 for leachable lead content per TCLP method

Cable Construction

Conductor: Bare copper Class B strand.
Strand Shield: A thermoset semi-conducting strand shield is extruded over the conductor.
Insulation: Tree-Retardant Cross-Linked Polyethylene (TR-XLPE).
Insulation Shield: A semi-conducting thermosetting layer, applied in a triple extrusion process, plus a helically applied gapped copper tape.
Color-Coded: Black, Red or Blue colored tape placed longitudinally under the copper tape shield.
Ground (Bonding) Conductor: The conductor consists of one uninsulated stranded bare copper conductor.
Inner Jacket: Flame-retardant Polyvinyl Chloride (PVC), UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option— Black.
Armor: Aluminum Interlocked Armor (AIA).
Overall Jacket: Flame-retardant Polyvinyl Chloride (PVC), UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option— Orange.

5kv CSA HVTECK

Cable Parameter

CON.
Size
(AWG/
kcmil)
Ground
Wire Size
AWG
Nominal Diameter (over) Appr. Cable Weight
W/AL Armor
Ampacity
(40°C
Ambient)
Insulation Insulation
Shield
Inner
Jacket
Armor CABLE LBS/
1000
FT
kg/km
Inches mm Inches mm Inches mm Inches mm Inches mm AL Steel AL Steel
6 8 0.39 9.91 0.47 11.94 1.17 29.7 1.45 36.9 1.54 39.2 1120 1590 1670 2360 93
4 8 0.43 10.92 0.51 12.95 1.26 32.0 1.54 39.1 1.63 41.4 1350 1850 1670 2760 122
2 6 0.49 12.45 0.57 14.48 1.39 35.3 1.67 42.4 1.77 45.0 1740 2290 2590 3410 159
1 6 0.52 13.21 0.60 15.24 1.45 36.9 1.73 43.9 1.83 46.5 1960 2540 2920 3780 184
1/0 6 0.56 14.22 0.63 16.00 1.53 38.9 1.81 46.0 1.91 48.5 2290 3010 3410 4490 211
2/0 6 0.60 15.24 0.67 17.02 1.62 41.2 1.91 48.5 2.01 51.1 2620 3380 3900 5030 243
3/0 4 0.64 16.26 0.71 18.03 1.78 45.2 2.07 52.6 2.17 55.1 3210 4040 4780 6020 279
4/0 4 0.70 17.78 0.76 19.30 1.90 48.3 2.19 55.6 2.29 58.2 3720 4600 5530 6840 321
250 4 0.75 19.05 0.82 20.83 2.01 51.1 2.30 58.4 2.43 61.8 4300 5240 6400 7800 355
350 3 0.85 21.59 0.96 24.38 2.32 58.9 2.61 66.3 2.74 69.6 5480 6520 8160 9700 435
500 3 0.97 24.64 1.04 26.42 2.48 63.0 2.77 70.4 2.90 73.7 7130 8280 10610 12320 536
750 2 1.15 29.21 1.24 31.50 2.98 75.7 3.27 83.1 3.42 86.9 10330 11700 15370 17410 668
1000 1 1.30 33.02 1.39 35.31 3.31 84.1 3.60 91.5 3.75 95.3 13080 14600 19460 21730 768