TRXLPE/Wire Shield/PVC/AIA/PVC, Power, Shielded,
Armored 5KV, CSA HVTECK, 133% Ins. Level, 115 Mils,
Single Conductor

Application

These cables are used in ventilated, non-ventilated and ladder type cable trays in dry, damp or wet locations, direct earth burial (with protection as required by inspection authority). They are exposed and concealed wiring in dry, damp or wet locations. Besides,the wires are in all hazardous locations when used with certified HL cable glands.

Standard:

CSA FT1 and FT4
IEEE 383 (70,000 BTU/hr), UL 1581 (70,000 BTU/hr)
IEEE 1202 (70,000 BTU/hr) CSA FT4
ICEA T-30-520 (70,000 BTU/hr)
ICEA T-29-520 (210,000 BTU/hr)
Hazardous location rating: HL
CSA Standard C68.3, C22.2 No. 174
CSA Approval (file) numbers: LR27161
Meets EPA 40 CFR, part 261 for leachable lead content per TCLP method

Cable Construction

Conductor: Bare copper Class B strand.
Strand Shield: A thermoset semi-conducting strand shield is extruded over the conductor.
Insulation: Tree-Retardant Cross-Linked Polyethylene (TR-XLPE).
Insulation Shield: A semi-conducting thermosetting layer, applied in a triple extrusion process, plus a concentric serving of solid copper wires acting as both a drain wire shield and as a grounding (bonding) conductor—Black.
Ground (Bonding) Conductor: The conductor is a concentric serving of solid copper wires applied over the thermosetting insulation shield.
Inner Jacket: Flame-retardant Polyvinyl Chloride (PVC), UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option— Black.
Armor: Aluminum Interlocked Armor (AIA).
Overall Jacket: Flame-retardant Polyvinyl Chloride (PVC), UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option— Orange.

5kv CSA HVTECK

Cable Parameter

NO.
of
CON.
CON.
Size
(AWG/
kcmil)
Ground
Wire Size
AWG
Nominal Diameter (over) Appr. Cable Weight
W/AL Armor
Ampacity
(40°C
Ambient)
Insulation Insulation
Shield
Inner
Jacket
Armor CABLE
Inches mm Inches mm Inches mm Inches mm Inches mm LBS/
1000
FT
kg/km In Air
1 6 8 0.44 11.2 0.51 13.0 0.73 18.6 0.95 24.2 1.04 26.4 550 820 112
1 4 6 0.48 12.3 0.55 13.9 0.77 19.6 0.99 25.2 1.08 27.5 680 1010 148
1 2 6 0.54 13.7 0.61 15.5 0.83 21.1 1.08 27.5 1.17 29.7 840 1250 195
1 1 4 0.57 14.5 0.64 16.3 0.91 23.0 1.16 29.5 1.25 31.8 960 1430 225
1 1/0 4 0.61 15.4 0.68 17.3 0.94 23.9 1.19 30.3 1.28 32.5 1060 1570 260
1 2/0 4 0.65 16.4 0.72 18.3 0.98 25.0 1.23 31.3 1.32 33.6 1170 1740 299
1 3/0 3 0.70 17.7 0.76 19.3 1.03 26.3 1.31 33.3 1.40 35.6 563 2000 345
1 4/0 3 0.75 18.9 0.81 20.6 1.08 27.5 1.36 34.6 1.45 36.9 710 2260 400
1 250 2 0.80 20.3 0.87 22.1 1.16 29.6 1.44 36.6 1.53 38.9 849 2580 444
1 350 1 0.94 23.9 1.01 25.7 1.29 32.8 1.57 39.9 1.67 42.4 1169 3230 549
1 500 1/0 1.02 26.0 1.11 28.2 1.41 35.8 1.69 43.0 1.79 45.6 1390 4260 688
1 750 2/0 1.20 30.6 1.29 32.8 1.60 40.7 1.89 48.0 1.99 50.6 2821 5860 889
1 1000 2/0 1.35 34.3 1.44 36.6 1.81 46.0 2.10 53.4 2.20 55.9 3608 7570 1061