Home ProuductsIndustrial Cables

TRXLPE/Wire Shield/PVC/AIA/PVC, Power, Shielded,
Armored 5KV, CSA HVTECK, 100% / 133% Ins. Levels, 90
Mils, Single Conductor

Application

These cables are used in ventilated, non-ventilated and ladder type cable trays in dry, damp or wet locations, direct earth burial (with protection as required by inspection authority). They are exposed and concealed wiring in dry, damp or wet locations. Besides,the wires are in all hazardous locations when used with certified HL cable glands.

Standard:

CSA FT1 and FT4
IEEE 383 (70,000 BTU/hr), UL 1581 (70,000 BTU/hr)
IEEE 1202 (70,000 BTU/hr) CSA FT4
ICEA T-30-520 (70,000 BTU/hr)
ICEA T-29-520 (210,000 BTU/hr)
Hazardous location rating: HL
CSA Standard C68.3, CSA Standard C22.2 No. 174
CSA Approval (file) numbers: LR27161
Meets EPA 40 CFR, part 261 for leachable lead content per TCLP method

Cable Construction

Conductor: Bare copper Class B strand.
Strand Shield: A thermoset semi-conducting strand shield is extruded over the conductor.
Insulation: Tree-Retardant Cross-Linked Polyethylene (TR-XLPE).
Insulation Shield: A semi-conducting thermosetting layer, applied in a triple extrusive process, plus a concentric serving of solid copper wires acting as both a drain wire shield and as a grounding (bonding) conductor—Black.
Ground (Bonding) Conductor: The conductor is a concentric serving of solid copper wires applied over the thermosetting insulation shield.
Inner Jacket: Flame-retardant Polyvinyl Chloride (PVC), UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option— Black.
Armor: Aluminum Interlocked Armor (AIA).
Overall Jacket: Flame-retardant Polyvinyl Chloride (PVC), UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option— Orange.

5kv CSA HVTECK

Cable Parameter

NO.
of
CON.
CON.
Size
(AWG/
kcmil)
Ground
Wire Size
AWG
Nominal Diameter (over) Appr. Cable Weight
W/AL Armor
Ampacity
(40°C
Ambient)
Insulation Insulation
Shield
Inner
Jacket
Armor CABLE
Inches mm Inches mm Inches mm Inches mm Inches mm LBS/
1000
FT
kg/km In Air
1 6 8 0.39 10.0 0.47 11.9 0.68 17.3 0.90 22.9 0.99 25.2 510 770 112
1 4 6 0.43 10.5 0.51 13.0 0.72 18.3 0.94 23.9 1.03 26.2 590 880 148
1 2 6 0.49 12.5 0.57 14.5 0.78 19.8 1.03 26.2 1.12 28.5 750 1120 195
1 1 4 0.52 13.3 0.60 15.3 0.81 20.6 1.06 27.0 1.15 29.2 870 1300 225
1 1/0 4 0.56 14.2 0.63 16.0 0.88 22.4 1.13 28.7 1.22 31.0 1010 1500 260
1 2/0 4 0.60 15.2 0.67 17.0 0.92 23.4 1.17 29.7 1.26 32.0 1120 1670 299
1 3/0 3 0.64 16.3 0.71 18.1 0.97 24.7 1.22 31.0 1.31 33.3 1300 1930 345
1 4/0 3 0.70 17.8 0.76 19.3 1.02 25.9 1.27 32.3 1.36 34.6 1470 2180 400
1 250 2 0.75 19.1 0.82 20.8 1.10 28.0 1.38 35.1 1.48 37.6 1680 2500 444
1 350 1 0.85 21.5 0.96 24.4 1.24 31.5 1.52 38.6 1.62 41.2 2120 3150 549
1 500 1/0 0.97 24.6 1.04 26.4 1.34 34.0 1.62 41.2 1.72 43.7 2770 4130 688
1 750 2/0 1.15 29.2 1.24 31.5 1.54 39.1 1.83 46.5 1.93 49.0 3780 5760 889
1 1000 2/0 1.30 33.0 1.39 35.3 1.76 44.7 2.05 52.1 2.15 54.6 5010 7460 1061