HomeProuductsIndustrial Cables

British Standard Industrial Cables
6181X/6182X/6183X/6184X/6185X to BS 7889

Application and Description

These cables are designed for surface wiring where there is little risk of mechanical damage and are suitable for use in electrical installations such as power and lighting.

Cable Construction

British Standard Industrial Cables
6181X/6182X/6183X/6184X/6185X to BS 7889British Standard Industrial Cables
6181X/6182X/6183X/6184X/6185X to BS 7889

  • - Bare copper conductor
    - Stranding to BS 6360 CL-2 or IEC 60228 CL-2
    - XLPE GP8 insulation
    - Inner covering (optional)
    - PVC sheath Type 9 to BS7655-4.2

Core Identification

  • 1-core: brown or blue;
    2-core: brown and blue;
    3-core: brown, black and grey;or green/yellow,brown and blue
    4-core: blue, brown, black and grey; or green/yellow, brown, black and grey
    5-core: greenlyellow, blue, brown, black and grey

Technical Characteristics

  • - Working voltage: 600/1000V
    - Minimum bending radius: OD<25 mm : 4xoverall diameter,
    OD>25 mm: 6xoverall diameter
    Shapped conductor: 6xoverall diameter
    - Operating temperature: -15º C to +90º C
    - Insulation resistance: 10 MΩxkm
    - Flame retardant: IEC 60332.1

Cable Parameter

Nominal Cross Sectional Area mm² Nominal Thickness of Insulation mm Nominal Thickness of Inner Covering mm Nominal Thickness of Sheath mm Nominal Cross Sectional Area mm² Nominal Thickness of Insulation mm Nominal Thickness of Inner Covering mm Nominal Thickness of Sheath mm
6181X 6182X
1.5 0.7 0.4 1.4 1.5 0.7 0.4 1.8
2.5 0.7 0.4 1.4 2.5 0.7 0.4 1.8
4 0.7 0.4 1.4 4 0.7 0.4 1.8
6 0.7 0.4 1.4 6 0.7 0.4 1.8
10 0.7 0.4 1.4 10 0.7 0.6 1.8
16 0.7 0.4 1.4 16 0.7 0.6 1.8
25 0.9 0.4 1.4 25 0.9 0.8 1.8
35 0.9 0.4 1.4 35 0.9 0.8 1.8
50 1.0 0.6 1.4 50 1.0 1.0 1.8
70 1.1 0.6 1.4 70 1.1 1.0 1.8
95 1.1 0.6 1.5 95 1.1 1.2 1.9
120 1.2 0.8 1.5 120 1.2 1.2 2.0
150 1.4 0.8 1.6 25 * 0.9 0.6 1.8
185 1.6 0.8 1.6 35 * 0.9 0.6 1.8
240 1.7 1.0 1.7 50 * 1.0 0.8 1.8
300 1.8 1.0 1.8 70 * 1.1 0.8 1.8
400 2.0 1.2 1.9 95 * 1.1 1.0 1.9
500 2.2 1.2 2.0 120 * 1.2 1.0 2.0
630 2.4 1.4 2.2 *Shaped stranded conductor
800 2.6 1.6 2.3
1000 2.8 1.6 2.4
Nominal Cross Sectional Area mm² Nominal Thickness of Insulation mm Nominal Thickness of Inner Covering mm Nominal Thickness of Sheath mm Nominal Cross Sectional Area mm² Nominal Thickness of Insulation mm Nominal Thickness of Inner Covering mm Nominal Thickness of Sheath mm
6183X 6184X
1.5 0.7 0.4 1.8 1.5 0.7 0.4 1.8
2.5 0.7 0.4 1.8 2.5 0.7 0.4 1.8
4 0.7 0.4 1.8 4 0.7 0.4 1.8
6 0.7 0.4 1.8 6 0.7 0.6 1.8
10 0.7 0.6 1.8 10 0.7 0.6 1.8
16 0.7 0.6 1.8 16 0.7 0.6 1.8
25 0.9 0.8 1.8 25 0.9 0.8 1.8
35 0.9 0.8 1.8 35 0.9 1.0 1.8
50 1.0 1.0 1.8 50 1.0 1.0 1.8
70 1.1 1.2 1.9 70 1.1 1.2 2.0
95 1.1 1.2 2.0 95 1.1 1.2 2.1
120 1.2 1.2 2.1 120 1.2 1.2 2.3
25 * 0.9 0.6 1.8 25 * 0.9 0.8 1.8
35 * 0.9 0.8 1.8 35 * 0.9 0.8 1.8
50 * 1.0 0.8 1.8 50 * 1.0 1.0 1.8
70 * 1.1 1.0 1.9 70 * 1.1 1.2 2.0
95 * 1.1 1.2 2.0 95 * 1.1 1.2 2.1
120 * 1.2 1.2 2.1 120 * 1.2 1.2 2.3
6185X
1.5 0.7 0.4 1.8 25 0.9 1.0 1.8
2.5 0.7 0.4 1.8 35 0.9 1.0 1.8
4 0.7 0.6 1.8 50 1.0 1.2 1.9
6 0.7 0.6 1.8 70 1.1 1.2 2.1
10 0.7 0.6 1.8 95 1.1 1.4 2.2
16 0.7 0.8 1.8 120 1.2 1.4 2.4