HomeProuductsHigh Voltage Cables

76/132kV XLPE Insulated, PE Sheathed High Voltage Power Cables

Application

These single core cables are designed for distribution of electrical power with nominal voltage 76/132kV. They are suitable for installation mostly in power supply stations, indoors and in cable ducts, outdoors, underground and in water as well as for installation on cable trays for industries, switchboards and power stations.

Standard

IEC 60840

Construction

76/132kV XLPE Insulated, PE Sheathed High Voltage Power Cables
Conductor The cable conductors can be made of copper or aluminium, depending on customer’s preference or current carrying capacity. Large size solid conductors are made of aluminium. Available constructions including: round solid conductors up to 2000mm^2 (RE); circular stranded compacted conductors up to 1200mm^2 (RM); circular conductors with shaped wires up to 2000mm^2 (RM, Keystone conductors); segmental conductors up to 2500 mm^2 (RMS, Milliken conductors); oval shaped stranded compacted conductors up to 800mm^2 for external gas pressure cables (OM).
Conductor Screen Extruded layer of semi-conducting cross-linkable compound is applied over the conductor and shall cover the surface completely.
Insulation Insulation is of cross-linked polyethylene compound XLPE.
Insulaton Screen Extruded layer of semi-conducting cross-linkable compound is applied over the insulation.
Metallic Layer The metallic layer may be applied over the core assembly collectively. The metallic screen shall consist of either copper tapes or a concentric layer of copper wires or a combination of tapes and wires.
Separation Sheath Aluminum Tape sheath.
Outer Sheath PE

Dimensional Data

Nom. Cross-Section Area Nom. Insulation Thickness Copper Wire Screen Area Approx. Overall Diameter Approx. Weight
CU AL
mm^2 mm mm^2 mm kg/m
185 22.0 50 74 6.0 4.4
240 20.0 50 72 6.2 4.3
300 19.0 50 72 6.8 4.5
400 18.0 50 74 7.7 5.2
500 18.0 50 77 8.8 5.7
630 18.0 50 81 10.3 6.4
800 16.0 50 82 11.7 6.8
1000 16.0 110 93 15.0 9.1
1200 15.0 110 94 17.0 9.7
1400 15.0 110 98 19.0 10.0
1600 15.0 110 101 21.0 11.0
1800 14.0 110 102 23.0 12.0
2000 14.0 110 106 25.0 13.0
2500 14.0 110 113 30.0 15.0

Electrical Data

Nom. Cross-Section Area D C Resistance @20°C A C Resistance @90°C Capacitance per core Inductance Current Ratings/PowerRatings (continuous load)
Cu conductor Al conductor
Cu Al Cu Al 1 circuit 2 circuits 1 circuit 2 circuits
mm^2 Ω/km Ω/km Ω/km Ω/km μF/km mH/km A/MVA A/MVA
              trefoil installation
185 0.0991 0.164 0.127 0.211 0.107 0.49 368/84 314/72 289/66 246/56
240 0.0754 0.125 0.0973 0.161 0.121 0.46 420/96 358/82 332/76 282/64
300 0.0601 0.100 0.0781 0.129 0.134 0.44 469/107 398/91 371/85 315/72
400 0.0470 0.0778 0.0618 0.101 0.151 0.42 525/120 444/102 420/96 356/81
500 0.0366 0.0605 0.0492 0.0791 0.163 0.40 586/134 493/113 474/108 400/91
630 0.0283 0.0469 0.0393 0.0622 0.177 0.39 649/148 545/125 533/122 448/102
800 0.0221 0.0367 0.0326 0.0500 0.212 0.36 706/161 591/135 591/135 495/113
              flat installation
1000 0.0176 0.0291 0.0232 0.0375 0.245 0.56 999/228 852/195 791/181 675/154
1200 0.0151 0.0247 0.0201 0.0319 0.271 0.55 1074/246 915/209 859/196 732/167
1400 0.0129 0.0212 0.0175 0.0275 0.286 0.53 1155/264 984/225 929/212 791/181
1600 0.0113 0.0186 0.0156 0.0240 0.301 0.52 1226/280 1043/238 997/228 849/194
1800 0.0101 0.0165 0.0142 0.0213 0.332 0.51 1285/294 1091/249 1058/242 900/206
2000 0.0090 0.0149 0.0129 0.0193 0.346 0.50 1346/308 1144/262 1114/255 947/217
2500 0.0072 0.0119 0.0109 0.0156 0.378 0.47 1465/335 1244/284 1244/284 1057/242