600/1000V ABC –Aerial Bundled Cables to HD 626 S1 (AL/XLPE)
Application
The aerial bundled cables designed for fixed installation as overhead power lines up to 1000 V incl.
Standard
HD 626 S1
Construction
Conductor |
Aluminium conductor, round stranded compressed (RM) |
Insulation |
XLPE |
Technical Data
Rated voltage |
kV |
0.6/1 |
Test voltage |
Veff kV/Hz |
4/50 |
Laying temperature |
°C |
min. -20 |
Operating temperature |
°C |
-30 bis +80 |
Conductor temperature |
°C |
max. +80 |
Short-circuit temperature |
°C/s |
max. +130 /5 |
Bending radius (min.) |
mm |
18 × Ø of cable |
Dimensions
Number of cores x nominal cross section |
min. breaking load of conductor strand |
Current rating in the air |
Outer diameter |
Total weight |
mm² |
kN |
A |
mm |
kg/km |
2x 16 RM |
1,910 |
2,5 |
72 |
147 |
2x 25 RM |
1,200 |
4,0 |
107 |
208 |
2x 35 RM |
0,868 |
5,5 |
132 |
277 |
2x 50 RM |
0,641 |
8,0 |
165 |
361 |
4x 16 RM |
1,910 |
2,5 |
72 |
286 |
4x 25 RM |
1,200 |
4,0 |
107 |
430 |
4x 35 RM |
0,868 |
5,5 |
132 |
553 |
4x 50 RM |
0,641 |
8,0 |
165 |
746 |
4x 70 RM |
0,443 |
10,7 |
205 |
1009 |
4x 95 RM |
0,320 |
13,7 |
240 |
1332 |
4x 120 RM |
0,253 |
18,6 |
290 |
1632 |
4x 35 + 1x 35 RM |
0,868/0,868 |
5,5/5,5 |
132/132 |
694 |
4x 50 + 1x 25 RM |
0,641/1,200 |
8,0/4,0 |
165/107 |
814 |
4x 50 + 1x 35 RM |
0,641/0,868 |
8,5/5,5 |
165/132 |
845 |
4x 70 + 1x 25 RM |
0,443/1,200 |
10,7/4,0 |
205/107 |
1105 |
4x 70 + 2x 25 RM |
0,443/1,200 |
10,7/4,0 |
205/107 |
1217 |
4x 70 + 1x 35 RM |
0,443/0,868 |
10,7/5,5 |
205/132 |
1150 |
4x 70 + 2x 35 RM |
0,443/0,868 |
10,7/5,5 |
205/132 |
1289 |
4x 95 + 1x 25 RM |
0,320/1,200 |
13,7/4,0 |
240/107 |
1438 |
4x 95 + 1x 35 RM |
0,320/0,868 |
13,7/5,5 |
240/132 |
1467 |
4x 95 + 2x 25 RM |
0,320/1,200 |
13,7/4,0 |
240/107 |
1544 |
other cross-sections on request