HomeProuductsUKOOA Offshore & Marine Cables

 UKOOA TYPE LA 600/1000V Flame Retardant

Application

These cables are designed for fixed installation for power, control and lighting in both and safe areas, emergency and critical offshore applications where cable protection is required.

Standards

BS 6883/BS 7917/UKOOA
IEC 60332-3-22 CAT. A
IEC 60332-1
IEC 60754-1 & IEC 60754-2
IEC 61034-1 & IEC 61034-2

Construction

Conductors Stranded class 2 or flexible class 5 tinned annealed copper conductors to BS 6360/IEC 60228.
Insulation EPR complying with BS7655 GP4 
Bedding CSP – SW2 compound complying with BS 7655. 
Armour  Tinned Phosphor Bronze Wire Braid to BS2873-PB102 (now BS EN 12166) 
Outer Sheath  CSP – SW2 compound complying with BS 7655.

Dimensions and Weight

Construction No. of cores×Cross section(mm²) Nominal Insulation Thickness mm Nominal Thickness of Inner Sheath mm Nominal Thickness of Outer Sheath mm Nominal Overall Diameter mm Approx. Weight kg/km
1×1.0 0.8 1.1 1.2 9.5 150
1×1.5 0.8 1.1 1.2 9.8 170
1×2.5 0.8 1.1 1.2 10.2 190
1×4 1.0 1.1 1.2 11.3 260
1×6 1.0 1.1 1.2 11.8 340
1×10 1.0 1.1 1.2 13.0 390
1×16 1.0 1.1 1.2 14.2 480
1×25 1.2 1.1 1.2 16.8 565
1×35 1.2 1.1 1.3 17.9 740
1×50 1.4 1.1 1.4 19.7 940
1×70 1.4 1.0 1.4 21.9 1270
1×95 1.6 1.2 1.4 24.5 1500
1×120 1.6 1.4 1.6 26.6 1750
1×150 1.8 1.6 1.8 29.0 2200
1×185 2.0 1.8 2.1 32.6 2700
1×240 2.2 1.3 1.5 36.0 3400
1×300 2.4 1.5 1.7 39.2 4200
1×400 2.6 1.7 2.0 43.7 5700
1×500 2.8 1.2 1.3 48.1 7200
1×630 2.8 1.0 1.2 52.3 8840