2YSLCY-JB/2YSLCYK-JB

Applications

These cables are double shielded, large gauge size, PVC motor supply cables Polyethylene insulation oververy fine stranded copper provides a low-loss transfer of power, excellent low capacitance performanceand superior flexibility when compared to conventional PVC cables. The applications include frequency converters, motor runs, connections with high electromagnetic interference. Found in the automotive, paperand food industry, environmental technology, packaging industry, machine tools and handling equipment. The overall foil and braid shield offer excellent protection against electromagnetic and electrical interferences. For medium mechanical stresses found indoors in dry, moist and wet areas. For 2YSLCYK-JB ,the black UVresistant jacket also allows for outdoor use and for direct burial applications.

Standards

  • VDE 0250 & 0281
  • EMC to EN 55011
  • EMC to VDE-0875 part-11
  • CE Low Voltage Directive 73/23/EEC
  • 93/68/EEC
  • ROHS compliant

Cable Construction

2YSLCY-JB/2YSLCYK-JB Motor Connecting Cables 2YSLCY-JB/2YSLCYK-JB Motor Connecting Cables
Stranded bare copper conductor according to DIN VDE 0295, IEC60228 cl. 5
Polyethylene(PE) insulation
Colours according to HD 308 S2(VDE 0293- 308)
Special aluminum foil screening
Tinned copper braiding, coverage approx. 80%
For 2YSLCY special transparent PVC sheath made of PVC compound YM2 acc. VDE 0207 -5, leadfree, flame retardant & self-extinguishing
For 2YSLCYK black PVC sheath made of cold-flexible PVC compound DMV5 acc. VDE 0276-603, leadfree, UV resistant, outdoor and direct burial use, flame retardant & self-extinguishing, IEC 60332.1 EEU directives cables conforms to EEC 79/29 directive ( Low Voltage Directive)

Technical Characteristics

Working voltage 600/1000 volts
Test voltage 4000 volts
Minimum bending radius 20 x O
Flexing temperature -5o C to +70o C
Fixed installation temperature - 40o C to +70o C
Flame retardant IEC 60332.1
Insulation resistance >20 GΩ x km
Coupling resistance max 250 Ω/km
Radiation resistance up to 80 x106 cJ/kg (up to 80 Mrad)
Mutual capacitance core/core 70 to 250 nF/km
core/braiding 110 to 410 nF/km

Cable Parameter

AWG No. of Cores x Nominal Cross Sectional Area Nominal Overall Diameter Mutual capacitance core/core approx. Mutual capacitance core/screen approx. Copper Weight Cable Weight
# x mm^2 mm nF/km nF/km kg / km kg / km
16(30/30) 4 G 1.5 11.6 70 110 95 230
14(50/30) 4 G 2.5 13.1 80 130 150.0 300
12(56/28) 4 G 4 14.6 90 150 235.0 485
10(84/28) 4 G 6 16.0 110 170 320.0 630
8(80/26) 4 G 10 19.5 120 190 533.0 860
6(128/26) 4 G 16 22.0 130 220 789.0 1,290
4(200/26) 4 G 25 26.2 145 230 1,236.0 1,860
2(280/26) 4 G 35 29.4 150 260 1,662.0 2,610
1(400/26) 4 G 50 37.5 175 290 2,345.0 2,950
2/0(356/24) 4 G 70 40.0 180 300 3,196.0 3,950
3/0(485/24) 4 G 95 46.4 195 320 4,316.0 5,300
4/0(614/24) 4 G 120 53.1 215 340 5,435.0 6,600
300 MCM (765/24) 4 G 150 57.2 230 360 6,394.0 7,043
350 MCM (944/24) 4 G 185 61.1 240 380 7639 8384
500 MCM 4 G 240 67.3 250 410 10013 11611