HomeProuductsMarine, OIL,GAS & Petrochemical Cables

 

Armoured 1kV Power

 

Armoured 1kV Power

Used extensively for power and control applications on ships and oil/gas platforms where mechanical protection and fire resistance to IEC60331 is required. These cables are also used for onshore applications where their combination of special properties make them ideal for essential services.

Colour Codes

a) Colour coded
1 Core Red or black
2 Core Red, black
3 Core Red, yellow, blue
4 Core Red, yellow, blue, black
5 Core and above Sequentially numbered

b) Number coded - most popular for stock items

Technical Information

Voltage rating 0.6/1kV
Conductors BS6360 class 2 or class 5 (Class 5 is generally manufactured to order)
Temperature rating +90°C maximum conductor temperature
Static temperature rating -30°C to +90°C
Bending radius (static) ≤ 25mm² 4 x cable O/D >  25mm² 6 x cable O/D
Flame retardant IEC60332 part 3A, BS4066 part 3A
Fire resistant IEC60331 (3 hours @ +750°C)
Technical Data
Nominal area of conductor mm Diameter over inner sheath min-max mm Diameter over outer sheath min-max mm
 Single-core cables
 1   5.1 - 6.3   8.0 - 9.2 
 1.5   5.4 - 6.6   8.2 - 9.4 
 2.5   5.8 - 7.0   8.8 - 10.0 
 4   6.7 - 8.0   9.7 - 10.9 
 6   7.2 - 8.5   10.3 - 11.7 
 10   8.1 - 9.5   11.4 - 12.8 
 16   9.3 - 10.7   12.6 - 14.0 
 25   11.5 -13.2   15.4 - 17.7 
 35   12.3 -14.1   16.5 - 18.8 
 50   14.1 -15.9   18.2 - 20.6 
 70   15.8 -17.8   12.2 - 23.0 
 95   18.1 -20.2   22.6 - 25.6 
 120   20.0 -22.4   24.7 - 27.7 
 150   22.0 -24.6   26.9 - 30.1 
 185   24.4 -27.0   30.0 - 33.6 
 240   27.5 -30.3   33.3 - 37.0 
 300   30.4 -33.6   36.4 - 40.2 
 400   34.1 -37.5   40.5 - 44.9 
 500   38.0 -41.5   44.7 - 49.3 
 630   41.6 -45.6   48.5 - 53.7 
 Two-core cables
 1   8.3 - 9.6   11.6 - 13.0 
 1.5   9.0 - 10.4   12.3 - 13.7 
 2.5   9.8 - 11.4   13.1 - 14.5 
 4   11.8 -13.5   15.7 - 18.0 
 6   12.9 -14.6   17.0 - 19.3 
 10   14.9 -16.8   19.0 - 21.4 
 16   17.1 -19.1   21.4 - 24.3 
 25   21.2 -23.7   25.9 - 29.0 
 35   23.1 -25.7   28.0 - 31.2 
 50   26.5 -29.2   32.3 - 38.5 
 70   30.3 -33.5   36.3 - 40.2 
 95   34.9 -38.2   41.2 - 45.7 
 120   38.4 -42.2   45.1 - 49.6 
 150   42.5 -46.5   49.4 - 54.7 
 185   47.1 -51.3   54.4 - 59.8 
 240   53.5 -58.2   61.3 - 67.5 
 300   59.3 -64.3   67.5 - 73.9 
Nominal area of conductor mm Diameter over inner sheath min-max mm Diameter over outer sheath min-max mm
 Three-core cables
 1   9.0 - 10.4   12.3 - 13.7 
 1.5   9.6 - 11.0   12.8 - 14.2 
 2.5   10.4 - 12.1   13.7 - 15.1 
 4   12.6 - 14.3   16.5 - 18.8 
 6   13.8 - 15.5   17.9 - 20.2 
 10   15.9 - 17.8   20.2 - 23.0 
 16   18.2 - 20.3   22.8 - 25.7 
 25   22.9 - 25.4   27.8 - 30.9 
 35   24.9 - 27.6   30.5 - 34.1 
 50   28.5 - 31.3   34.3 - 38.1 
 70   32.7 - 35.9   38.8 - 43.2 
 95   37.5 - 41.0   44.1 - 48.6 
 120   41.3 - 45.3   48.3 - 53.4 
 150   45.8 - 49.9   52.9 - 58.2 
 185   50.9 - 55.5   58.6 - 64.6 
 240   57.5- 62.4   65.6 - 71.9 
 300   64.0 - 69.4   72.6 - 79.6 
 Four-core cables
 1   9.8 - 11.4   13.1 - 14.5 
 1.5   10.5 - 12.1   13.7 - 15.1 
 2.5   11.4 - 13.1   15.4 - 17.6 
 4   13.8 - 15.6   17.9 - 20.3 
 6   15.3 - 17.3   19.6 - 22.5 
 10   17.7 - 19.7   22.2 - 25.1 
 16   20.3 - 22.8   25.0 - 28.1 
 25   25.5 - 28.1   31.0 - 34.7 
 35   27.7 - 30.5   32.5 - 37.2 
 50   31.8 - 35.0   37.9 - 41.8 
 70   36.3 - 39.7   42.9 - 47.4 
 95   41.7 - 45.7   48.6 - 53.8 
 120   46.2 - 50.3   53.5 - 58.9 
 150   51.1 - 55.7   58.7 - 64.7 
 185   56.8 - 61.6   64.3 - 71.1 
 240   64.3- 69.8   73.0 - 80.0 
 300   71.5 - 77.6   80.7 - 88.4 
 Five-core cables and above
 5x1.5   11.4 - 13.1   15.4 - 17.6 
 7x1.5   12.6 - 14.4   16.6 - 18.9 
 12x1.5   16.8 - 18.8   21.2 - 24.0 
 19x1.5   19.9 - 22.4   24.4 - 27.5 
 27x1.5   24.3 - 26.9   29.2 - 32.8 
 37x1.5   27.4 - 30.4   33.0 - 36.7 
 5x2.5   12.7 - 14.4   16.6 - 18.9 
 7x2.5   13.9 - 15.6   18.0 - 20.3 
 12x2.5   18.7 - 20.8   23.2 - 26.2 
 19x2.5   22.1 - 24.7   26.8 - 30.0