HomeProuductsMineral insulated cables & Heating cables

Heating Tape for Corrosive Environments

Heating Tape for Corrosive Environments

Application

Heat tracing on apparatus, appliances and systems
Temperature maintenance on piping
Laboratory applications

Standard

DIN VDE 0253

Voltage Rating

230V

Construction

Heating conductor
Insulation: Fluoropolymer.
Protective: 1.4301 / SS 304.

Mechanical and Thermal Properties

Maximum operating temperature: 260℃
Minimum installation temperature: -30℃
Minimum bending radius flat: 15 mm
Maximum output: 50 W/m
Approx Dimensions : 10 x 5 mm
Dimensions, sleeve: 32 x 16 x 65 mm

Cable Parameter

Heated length Nominal output
Maximum temperature 100 °C Maximum temperature 150 °C Maximum temperature 200 °C
0.6 30 - -
1.1 54 - -
1.7 78 52 26
2.4 94 69 37
3.0 147 88 44
4.2 210 126 63
5.4 245 163 82
6.0 294 176 88
7.0 344 - -
10.0 464 294 -
12.5 623 371 192
15.0 705 441 220
17.5 864 521 -
21.0 1008 611 315
28.0 1390 756 378